Max. 70C outlet water temperature;
R134a refrigerant;
Ideal refurbishement for old buildings heating system;
Siemens controller, easily understandable control
Scroll compressor;
Plate type heat exchanger.
Varied heat curve
| Heat pump |
Type |
GSWW8/H |
GSWW10/H |
| Dimensions,weights,connection dimensions |
| Dimensions |
HxWxD |
960x600X600 |
| Weight |
kg |
110 |
120 |
| Refrigerant |
Type |
R134a |
| Filling weight |
kg |
2 |
2.3 |
| Permissible operating pressure |
Mpa |
3 |
3 |
| Pipe connector-hot side |
Inch |
G1” |
G1” |
| Pipe connector-cold side |
Inch |
G1” |
G1” |
| Evaporator |
Type |
Brazed plate heat exchanger |
| Condenser |
Type |
Brazed plate heat exchanger |
| Compressor |
|
1xScroll |
1xScroll |
| Performance Heat pump |
| Heat output |
at B0/W35(1) |
kW |
8 |
9.8 |
| Power consumption |
kW |
1.9 |
2.34 |
| Performance factor |
|
4.21 |
4.19 |
| Heat output |
at W10/W35(2) |
kW |
10.1 |
12.5 |
| Power consumption |
kW |
1.89 |
2.33 |
| Performance factor |
|
5.34 |
5.36 |
| Usage limit |
|
|
B-15/W40 W5/W70 |
| Process medium |
|
Brine/water values in [ ] |
| Process medium |
|
Brine made from water with 33Vol.% ethylene glycol |
| Volume flow |
hot side |
m3/h |
1.74[1.4] |
2.2[1.7] |
| cold side |
m3/h |
1.4[1.3] |
1.8[1.6] |
| Power |
Type |
Triple phase |
Triple phase |
| Sound power level |
dB(A) |
46 |
47 |
| (1)B0/W35=Brine water inlet temperature 0℃,heating flow 35℃ |
|
| (2)W10/W35=Well water inlet temperature 10℃,heating flow 35℃ |
|