| AIR TO WATER HEAT PUMP |
AW13/H |
| Heat output/Power consumption at 7/35℃ |
kW |
13.0/3.3 |
| Heat output/Power consumption at 7/45℃ |
kW |
12.5/3.9 |
| Heat output/Power consumption at 7/65℃ |
kW |
12.3/5.1 |
| Heat output/Power consumption at -7/35℃ |
kW |
9.0/3.4 |
| Heat output/Power consumption at -7/45℃ |
kW |
8.9/4.1 |
| Heat output/Power consumption at -7/65℃ |
kW |
8.8/4.8 |
| Starting current |
A |
52 |
| Power |
|
380-415V/3PH/50Hz |
| Compressor |
|
HITACHI EVI Scroll |
| Condenser |
|
Brazed plate heat exchanger |
| Nominal flow heating medium |
l/s |
0.31 |
| Internal pressure drop at nominal flow |
kPa |
5 |
| Air flow |
m3/h |
5000 |
| Nominal output fan |
W |
300 |
| Max outgoing heating medium temperature |
℃ |
65 |
| Dimensions(HxWxD) |
mm |
1075x1105x505 |
| Pipe connector |
|
DN25 |
| Weight |
kg |
175 |